ESD Unifloor® Static Dissipative Vinyl Sheet Flooring
ESD Unifloor® Static Dissipative Vinyl Sheet Flooring offers the following features and installation guide:
Installation
Concrete sub-floors must be constructed as perAmerican Concrete Institute 302.2 “Guide for Concrete Slabs that Receive Moisture Sensitive Flooring” and prepared according to ASTM F710 “Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring”.
Sub-floors must be tested for moisture prior to installation.
- Test per ASTM F 1869 “Standard Test Method for Moisture Vapor Emission Rate of Concrete Sub- floors Using Anhydrous Calcium Chloride ” One test should be conducted for each 1,000 s. Moisture limits are < 3.0/lb./1000 s. in 24 hours.
- Test per ASTM F2170 “Standard Test Method for Determining Relative Humidity in Concrete Floors using in-situ probes. Moisture Limit is < 80% Relative Humidity.
- The pH of the sub-floor should be between 7-9